UltraDb
Log in Get started
<- Reference

Surge

Surge Arresters, Medium- and High-Voltage - Acceptance Test

What it is

The acceptance test of a medium- or high-voltage surge arrester is a sequence of visual, mechanical, and electrical checks performed on a new or reconditioned arrester before it is placed into service on a substation or transmission structure. The test identifies the arrester by manufacturer, model number, serial number, and maximum continuous operating voltage (MCOV) in kV; verifies that it is clean and free of physical damage or corrosion; and confirms the quality of its bolted electrical connections, the integrity of its grounding connection, and its insulation condition through resistance, insulation-resistance, and (for station-class arresters) watts-loss measurements. NETA ATS-2025 section 7.19.2 defines this battery of tests for station-class, intermediate-class, and distribution-class arresters installed to protect transformers, bus, circuit breakers, transmission lines, or other energized equipment from transient overvoltages caused by lightning or switching surges.

Why it is performed

A surge arrester is the front line of defense against damage from lightning strikes and switching transients, but only if it is installed correctly and functions without internal or external defects when the surge arrives. Contamination, shipping damage, improper storage, corrosion of the grounding connection, or a manufacturing flaw can render an arrester inoperative - and if the arrester fails silently rather than obviously, the protected equipment will be without defense during the next nearby lightning event. Acceptance testing confirms that the arrester is in condition to perform its duty and provides a baseline of electrical properties against which future maintenance measurements can be compared.

When it is performed

Acceptance testing is performed on every new or reconditioned surge arrester before it is energized, typically as a formal, documented step before the arrester is mounted on its line or structure and its ground connection is made permanent. The test is part of the substation acceptance sequence and is carried out during the installation or energization hold-off, not deferred to a later maintenance interval.

How it is typically performed

With the arrester de-energized and isolated, visual inspection begins: the arrester is examined for shipping damage, cracks in the porcelain or polymeric housing, surface contamination, and corrosion at the grounding lug or mounting hardware. The nameplate is read and cross-checked against the design documents to confirm the MCOV, arrester class (station, intermediate, or distribution), phase designation, and other identifying data are correct. Bolted-connection resistance is measured at each phase's line and ground lead terminations and compared against similar connections on the same installation, flagging any joint that reads meaningfully higher than the others as a possible loose or corroded connection. The arrester's grounding connection is tested separately, using the ground-resistance test method described elsewhere in NETA ATS-2025, to confirm that the path from the arrester's ground terminal to the station ground system is intact and of low resistance. Insulation-resistance measurements across the main arrester element, from each phase terminal to ground, are taken with a megohmmeter at a test voltage appropriate to the arrester's voltage class and recorded, giving a snapshot of the dielectric condition before the arrester is energized. For station-class arresters, a watts-loss test is also performed, applying an AC test voltage across the arrester and measuring the resulting power loss in each phase for comparison against similar units.

What gets recorded

Arrester identification: manufacturer, model number, serial number, phase, class (station, intermediate, distribution), MCOV in kV, and equipment designation (the transformer, bus section, or line it will protect). Visual-inspection findings: condition of the housing (clean or contaminated, undamaged or damaged), grounding-connection condition (clean or corroded), and any deviations from the design nameplate. Electrical measurements: bolted-connection resistance at each phase's terminations, the grounding connection's resistance to the station ground system, insulation resistance in megohms at the specified test voltage, and, for station-class arresters, watts-loss in watts per phase, taken and recorded alongside the test instrument identification, ambient temperature, and date and time of the test.

How results are evaluated

NETA ATS-2025 section 7.19.2 requires that the arrester be free of physical damage and corrosion, that its nameplate data match the equipment design, that bolted-connection resistance not deviate significantly from similar connections on the same installation, that the grounding-connection resistance fall below a small fixed threshold set out in the purchased standard, and that its insulation-resistance measurement exceed a minimum threshold that depends on the arrester's voltage class and type. For station-class arresters, watts-loss results are evaluated by comparison with similar units and the test-equipment manufacturer's published data rather than against a fixed numeric limit. An arrester with visible damage, a nameplate mismatch, a high-resistance bolted or grounding connection, or an insulation-resistance or watts-loss reading outside its expected range is not accepted into service and is returned to the manufacturer for repair or replacement. See the purchased standard for the complete acceptance criteria and any arrester-type or voltage-class-specific exceptions.

Governing standards

ANSI/NETA ATS-2025

ANSI/NETA ATS-2025

Purchase this standard ↗

Run this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, and NETA standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies.