UltraDb
Log in Get started
<- Reference

Rotating Machinery and Motor Control

Medium-Voltage Motor Control Center Acceptance Test

What it is

The medium-voltage motor control center (MCC) acceptance test is a systematic inspection and functional verification procedure applied to a new or reconditioned motor control center - a switchboard or cabinet housing medium-voltage power distribution, vacuum or SF6 contactors, motor starters, protective relays, metering, and control circuits - before it is first energized and placed into service. Per NETA ATS-2025 7.16.2.2, the test captures the center's identification (manufacturer, model, serial number, rated voltage, bus current rating, short-circuit rating, phase configuration, and number of vertical sections), documents any existing damage or defects discovered during visual and mechanical inspection, and confirms that each motor starter, contactor, relay, instrument transformer, and interconnecting bus or cable meets its own acceptance criteria when tested in isolation or as an assembled system.

Why it is performed

A motor control center is the gateway between the plant's primary distribution system and the individual motor loads it serves. Any defect in the center itself - a loose connection, a miswired control circuit, contamination in a vacuum or SF6 interrupter, or a relay that does not calibrate to nameplate - can prevent a motor from starting cleanly, prevent a fault from being cleared, or create a shock or arc hazard during operation. Confirming the center as a whole and all of its constituent devices before energization ensures that faults are caught and remedied while the unit is still on the workbench and de-energized, rather than discovered through an outage or personnel injury after installation.

When it is performed

Acceptance: performed once, before a new or reconditioned motor control center is placed into service. The acceptance sequence typically runs alongside a broader electrical test battery that includes insulation resistance on all bus and coil circuits, contact resistance on mains disconnects and interrupters, vacuum or SF6 pressure measurements, protective relay calibration, and instrument transformer turns ratio, so that all devices and circuits are confirmed in a single coordinated campaign rather than haphazardly over weeks or months. Maintenance: a periodic re-inspection and re-test of selected items may be called for by plant standards or regulatory requirement, but the full acceptance battery is not routinely repeated unless the center is removed from service and reconditioned.

How it is typically performed

With the motor control center de-energized, locked out, and tagged per site safety procedures, the acceptance test begins with a visual inspection of the exterior for shipping damage, dents, or corrosion, and of the interior for contamination, loose fasteners, foreign material, or evidence of overheating such as discoloration or burn marks on contacts or bus. Each motor starter or contactor is then tested per its own acceptance standard (vacuum contact gap, SF6 pressure, coil resistance and insulation resistance, contact resistance, and mechanical operation), and any protective relay is calibrated and verified against its trip-curve data sheet. Instrument transformers (CTs and PTs) are checked for turns ratio and insulation integrity. The main bus and all branch circuits are measured for insulation resistance to ground and to phase, and for continuity. The control power transformer, if present, is tested for turns ratio and insulation. All measured values and observations are recorded against a checklist that references each individual acceptance standard so that a supervisor or customer can see at a glance which tests passed and which items require rework before the center is accepted.

What gets recorded

Equipment identification: manufacturer, model/catalog number, serial number, rated voltage, bus current rating in amperes, short-circuit rating in kiloamperes, phase (single-phase or three-phase), number of vertical sections or compartments, and the center's designation or service name in the plant. For each motor starter, contactor, protective relay, instrument transformer, and bus or coil circuit tested: the test date, ambient temperature, test-instrument make/model/serial and calibration date, the measured value (insulation resistance, contact resistance, relay pickup setting, CT ratio, etc.), the acceptance limit or tolerance from the applicable standard, and pass or fail status. Any defect discovered during visual inspection, any damage noted, and any rework or repair performed is documented with the date and the technician's initials.

How results are evaluated

NETA ATS-2025 7.16.2.2 does not specify a single numeric acceptance criterion for the control center as a whole; instead, it requires that the center be documented by identification, and that each constituent device and circuit be evaluated against its own acceptance standard - the vacuum interrupter against NETA or IEEE criteria for contact gap and dielectric withstand, the contactor coil against insulation-resistance limits, the protective relay against its calibration tolerance, and so on. A motor control center is deemed acceptable when all of its devices and circuits individually meet their respective acceptance criteria, all visual defects have been corrected, and the documentation is complete and signed off. See the purchased standard for the full checklist of required tests and the cross-reference to the specific acceptance criteria for each device type.

Governing standards

ANSI/NETA ATS-2025

ANSI/NETA ATS-2025

Purchase this standard ↗

Run this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, and NETA standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies.