UltraDb
Log in Get started
<- Reference

Instrument Transformers

Voltage Transformer Acceptance Test

What it is

The voltage transformer (VT) acceptance test is a suite of electrical and physical measurements performed on newly installed or reconditioned potential transformers before they are put into service. The test verifies that the transformer accurately steps down a primary voltage to the secondary voltage level expected by metering and protection circuits, and captures the instrument's nameplate and as-found electrical condition. NETA ATS-2025 section 7.10.2 outlines the required identification data and acceptance criteria for voltage transformers installed on medium-voltage and high-voltage power systems. Testing includes documenting manufacturer, model and catalog number, serial number, voltage ratio, primary and secondary voltages, basic impulse level (BIL), accuracy class, rated burden, insulation class, phase designation, and equipment location, alongside measurements that confirm the transformer's accuracy and insulation integrity before energization.

Why it is performed

A voltage transformer supplies the potential signal that metering devices, protective relays, and supervisory systems depend on to monitor, measure, and control the power system. If a VT is installed incorrectly, damaged in transit, or misconfigured at the secondary, the voltage signal seen by those devices will be wrong - potentially causing meters to read inaccurately, relays to misoperate, or alarms to trigger on phantom conditions. Confirming the VT's nameplate specifications, voltage ratio, burden, accuracy class, and insulation before the unit is energized ensures that downstream metering and protection functions receive the signal they expect and can respond correctly to actual system events.

When it is performed

Acceptance: performed on every newly installed or reconditioned voltage transformer as part of the electrical test plan before the instrument is connected to the power system and its secondary winding is energized. The test is typically run in the shop or field once the VT is in place and de-energized, and must be completed before the metering circuits and protective relay inputs are commissioned downstream. Maintenance: not generally repeated on a schedule; the acceptance test is the baseline, and degradation is typically detected by comparing in-service secondary voltage readings or relay performance against the acceptance result rather than by running the full acceptance suite again.

How it is typically performed

With the voltage transformer de-energized and isolated, the technician first verifies and documents all nameplate information: manufacturer, model, serial number, voltage ratio (primary to secondary), primary and secondary voltages, BIL rating, accuracy class, rated burden in volt-amperes, insulation class, phase designation, and the equipment designation or location the VT serves. A visual inspection confirms no damage, corrosion, or contamination that could impair performance. Electrical tests follow: insulation resistance is measured winding-to-winding and each winding-to-ground, applying the test voltage appropriate to the transformer's coil rating for one minute; polarity is checked and must agree with the transformer's nameplate markings; and a ratio (turns-ratio) test verifies the transformer's ratio error is within the limits appropriate to its application, with revenue-metering VTs held to a tighter ratio and phase-angle tolerance than general-purpose VTs. Measured burden is compared to the transformer's rated burden. For primary windings rated 15 kV and higher, a dielectric withstand test and a power-factor or dissipation-factor test are also performed, each judged against the manufacturer's published data. The technician confirms that the secondary circuit is grounded at one point only and that no open circuits or shorts exist in the secondary winding.

What gets recorded

All nameplate data: manufacturer, model and catalog number, serial number, VT ratio, primary voltage, secondary voltage, BIL (in kV), accuracy class, rated burden, insulation class, phase, and equipment designation. As-found electrical measurements: insulation resistance readings (winding-to-winding and each winding-to-ground), the polarity result, ratio-error (turns-ratio) results at the tap or taps tested, the measured burden, and - for primary windings rated 15 kV and higher - the dielectric withstand result and the power-factor or dissipation-factor result, along with any visual inspection notes (damage, contamination, or corrosion). Ambient temperature, test-instrument identification, and the date and technician name or identifier are captured so results can be audited and reproduced.

How results are evaluated

NETA ATS-2025 section 7.10.2 requires that the voltage transformer's nameplate information be verified against the application requirements and that the transformer be free of visible damage, corrosion, or contamination that could degrade insulation or accuracy. Polarity results must agree with the transformer's markings. Ratio error is judged against the accuracy class and the application - revenue-metering VTs are held to a tighter ratio and phase-angle tolerance than general-purpose VTs, per IEEE C57.13.8.1.1. Measured burden is compared to the transformer's rated burden, confirming the ratio and burden design are correct for the metering and protection circuits the VT supplies. Insulation resistance, where measured, must meet the minimum appropriate for the transformer's voltage class and insulation system, and the secondary circuit must be grounded at one point only. For primary windings rated 15 kV and higher, the dielectric withstand test must run its full duration with no evidence of distress or insulation failure, and power-factor or dissipation-factor results are judged against the manufacturer's published data. A voltage transformer that fails to meet these criteria, shows signs of damage, or exhibits insulation degradation is not energized; it is investigated, repaired, or replaced before being returned to service. See the purchased standard for the complete identification and acceptance criteria.

Governing standards

ANSI/NETA ATS-2025

ANSI/NETA ATS-2025

Purchase this standard ↗

Run this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, and NETA standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies.