UltraDb
Log in Get started
<- Reference

Sectionalizer

Automatic Line Sectionalizers, Oil - Acceptance Test

What it is

An automatic line sectionalizer is an oil-filled switchgear device that detects a sustained fault current on a distribution line, counts a preset number of reclosing cycles, and locks itself open after the count is reached to isolate the faulted section without manual intervention. The acceptance test verifies that the device meets its nameplate ratings and baseline performance before it is energized for the first time. NETA ATS-2025 section 7.24.2 calls out identification of the unit (manufacturer, model, serial number, phase configuration, rated voltage, continuous current rating, insulating liquid type, and counts-to-lockout setting), measurement of bolted connection resistance at each phase, visual inspection of the housing and liquid condition, and verification that the operating mechanism responds and counts correctly when the trip coil is energized.

Why it is performed

An oil-filled sectionalizer must reliably detect fault currents and count reclosing operations without false trips at normal load current, and must isolate a faulted section before damage propagates to healthy parts of the network. Connection resistance that is elevated due to corrosion, debris, or poor assembly introduces voltage drop and heating that can degrade performance or shorten component life. Confirming the device's baseline resistance, liquid condition, and mechanical response before it is placed into service prevents unexpected failures that would otherwise remain hidden until a real fault occurs.

When it is performed

Acceptance: run before a new or reconditioned oil-filled sectionalizer is first energized and placed on the line. The test is performed after the unit is received and installed at the substation, with the device isolated from the live line and de-energized per standard safety procedures. Maintenance: the connection resistance measurement and visual inspection are often repeated on a periodic interval or after a significant event such as a through-fault or oil-level service.

How it is typically performed

With the sectionalizer de-energized, isolated, and grounded, the nameplate data (manufacturer, model, serial number, rated voltage, continuous current rating, phase count, liquid type, and lockout count setting) are recorded. Bolted connection resistance at each phase is measured using a low-resistance ohmmeter or a four-wire resistance instrument, applied between the incoming and outgoing terminals of the device to capture the total resistance of the bolted joints and any internal contacts in series. The insulating liquid is inspected visually for color, clarity, and any free water or sediment; a sample may be drawn per ASTM D923 for laboratory analysis (acid number, water content, breakdown voltage, power factor) if field observations raise concern. The operating mechanism is then exercised: with the trip coil de-energized, the manual or motorized charging handle is cycled to close the contacts, and then the trip coil is energized to open them; this sequence is repeated to confirm the count mechanism advances with each trip and does not advance during normal operation, and to verify that the device locks open after the preset count is reached.

What gets recorded

The identification section captures manufacturer, model, catalog number, serial number, rated voltage, continuous current rating in amperes, phase configuration (single-phase or three-phase), insulating liquid type, counts-to-lockout setting, and equipment designation or location. Bolted connection resistance in microhms for each phase (A, B, C where applicable). Results of the visual inspection: condition of the housing, color and clarity of the liquid, any evidence of water or sediment, and leakage. Results of the mechanism test: whether the device charged and opened correctly, whether the count mechanism advanced as expected, and whether the device locked open after the programmed number of trips. Ambient temperature, test-instrument identification, and test date are recorded alongside these readings.

How results are evaluated

NETA ATS-2025 section 7.24.2 specifies that bolted connection resistance at each phase must be low enough to meet the equipment manufacturer's published limits or, if those are not available, must not exceed values that would cause unacceptable voltage drop or heating during continuous rated current. The insulating liquid must meet new-liquid or in-service limits for color, acid number, water content, and dielectric breakdown voltage, as given in NETA ATS-2025 Tables 100.4.1 through 100.4.3 depending on liquid type. The operating mechanism must respond cleanly to the charging and trip commands, must advance its counter with each trip and not during normal operation, and must lock the device open after the count reaches the nameplate-specified lockout threshold without manual reset. Any measurement outside the manufacturer's published range, any visual evidence of contamination or damage to the housing or liquid, or any malfunction of the mechanism warrants investigation and remediation before the device is energized. See the purchased standard for the complete acceptance criteria and any device-specific exceptions.

Governing standards

ANSI/NETA ATS-2025

ANSI/NETA ATS-2025

Purchase this standard ↗

Run this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, and NETA standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies.